RETFLEX N2XY 0,6/1 kV Multi-core with Insulated Grounding Conductor; METRIUM

Products

RETFLEX N2XY 0,6/1 kV 2x4+1x4 mm2 FB

Nexans ref. P00020493-7 - Country ref. 10040152

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 2
  • Conductor cross-section: 4 mm²
  • Conductor diameter: 2.5 mm
  • Minimum insulation thickness: 0.7 mm
  • Ground conductor cross-section: 4 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 11.1 mm
  • Approximate weight: 195 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x4+1x4 mm2 FB

Nexans ref. P00020487-9 - Country ref. 10040146

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 4 mm²
  • Conductor diameter: 2.5 mm
  • Minimum insulation thickness: 0.7 mm
  • Ground conductor cross-section: 4 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 12.1 mm
  • Approximate weight: 232 kg/km

 

RETFLEX N2XY 0,6/1 kV 2x6+1x6 mm2 FB

Nexans ref. P00020494-6 - Country ref. 10040153

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 2
  • Conductor cross-section: 6 mm²
  • Conductor diameter: 3.0 mm
  • Minimum insulation thickness: 0.7 mm
  • Ground conductor cross-section: 6 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 12.3 mm
  • Approximate weight: 258 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x6+1x6 mm2 FB

Nexans ref. P00020488-7 - Country ref. 10040147

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 6 mm²
  • Conductor diameter: 3.0 mm
  • Minimum insulation thickness: 0.7 mm
  • Ground conductor cross-section: 6 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 13.5 mm
  • Approximate weight: 322 kg/km

 

RETFLEX N2XY 0,6/1 kV 4x6+1x6mm2

Nexans ref. P00020540-7 - Country ref. 10040167

  • Outer sheath: PVC Flexible
  • Number of cores: 4
  • Conductor cross-section: 6 mm²
  • Conductor diameter: 3.0 mm
  • Minimum insulation thickness: 0.7 mm
  • Ground conductor cross-section: 6 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 14.7 mm
  • Approximate weight: 406 kg/km

 

RETFLEX N2XY 0,6/1 kV 2x10+1x10 mm2 FB

Nexans ref. P00020496-6 - Country ref. 10040155

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 2
  • Conductor cross-section: 10 mm²
  • Conductor diameter: 4.3 mm
  • Minimum insulation thickness: 0.7 mm
  • Ground conductor cross-section: 10 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 15 mm
  • Approximate weight: 424 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x10+1x10 mm2 FB

Nexans ref. P00020486-8 - Country ref. 10040145

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 10 mm²
  • Conductor diameter: 4.3 mm
  • Minimum insulation thickness: 0.7 mm
  • Ground conductor cross-section: 10 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 16.5 mm
  • Approximate weight: 522 kg/km

 

RETFLEX N2XY 0,6/1 kV 4x10+1x10mm2 FB

Nexans ref. P00020550-7 - Country ref. 10050584

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 4
  • Conductor cross-section: 10 mm²
  • Conductor diameter: 4.3 mm
  • Minimum insulation thickness: 0.7 mm
  • Ground conductor cross-section: 10 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 18.1 mm
  • Approximate weight: 652 kg/km

 

RETFLEX N2XY 0,6/1 kV 2x16+1x16mm2 FB

Nexans ref. P00024231-2 - Country ref. 10042566

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 2
  • Conductor cross-section: 16 mm²
  • Conductor diameter: 5.3 mm
  • Minimum insulation thickness: 0.7 mm
  • Ground conductor cross-section: 16 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 17.5 mm
  • Approximate weight: 571 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x16+1x16 mm2 FB

Nexans ref. P00020490-9 - Country ref. 10043995

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 16 mm²
  • Conductor diameter: 5.3 mm
  • Minimum insulation thickness: 0.7 mm
  • Ground conductor cross-section: 16 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 19.2 mm
  • Approximate weight: 713 kg/km

 

RETFLEX N2XY 0.6/1 kV 4x16+1x16mm2 FB

Nexans ref. P00020552-10 - Country ref. 10050583

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 4
  • Conductor cross-section: 16 mm²
  • Conductor diameter: 5.3 mm
  • Minimum insulation thickness: 0.7 mm
  • Ground conductor cross-section: 16 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 21.1 mm
  • Approximate weight: 887 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x25+1x16 mm2 FB

Nexans ref. P00008539-10 - Country ref. 10042715

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 25 mm²
  • Conductor diameter: 6.6 mm
  • Minimum insulation thickness: 0.9 mm
  • Ground conductor cross-section: 16 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 22.5 mm
  • Approximate weight: 1015 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x25+1x25 mm2 FB

Nexans ref. P00020492-8 - Country ref. 10044658

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 25 mm²
  • Conductor diameter: 6.6 mm
  • Minimum insulation thickness: 0.9 mm
  • Ground conductor cross-section: 25 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 23.7 mm
  • Approximate weight: 1120 kg/km

 

RETFLEX N2XY 0,6/1 kV 4x25+1x16mm2 FB

Nexans ref. P00006752-3 - Country ref. 10032868

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 4
  • Conductor cross-section: 25 mm²
  • Conductor diameter: 6.6 mm
  • Minimum insulation thickness: 0.9 mm
  • Ground conductor cross-section: 16 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 26.1 mm
  • Approximate weight: 1279 kg/km

 

RETFLEX N2XY 0,6/1 kV 4x25+1x25mm2 FB

Nexans ref. P00039182-DB-2 - Country ref. 10053624

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 4
  • Conductor cross-section: 25 mm²
  • Conductor diameter: 6.6 mm
  • Minimum insulation thickness: 0.9 mm
  • Ground conductor cross-section: 25 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 26.1 mm
  • Approximate weight: 1390 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x35+1x16 mm2 FB

Nexans ref. P00020452-7 - Country ref. 10040105

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 35 mm²
  • Conductor diameter: 7.8 mm
  • Minimum insulation thickness: 0.9 mm
  • Ground conductor cross-section: 16 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 24.9 mm
  • Approximate weight: 1326 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x35+1x35mm2 FB

Nexans ref. P00010389-9 - Country ref. 10029759

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 35 mm²
  • Conductor diameter: 7.8 mm
  • Minimum insulation thickness: 0.9 mm
  • Ground conductor cross-section: 35 mm²
  • Minimum outer sheath thickness: 1.2 mm
  • Diameter over Sheath: 26.4 mm
  • Approximate weight: 1520 kg/km

 

RETFLEX N2XY 0,6/1 kV 4x35+1x25mm2 FB

Nexans ref. P00039706-0 - Country ref. 10054147

  • Packaging: Drum
  • Outer sheath: PVC Flexible
  • Number of cores: 4
  • Conductor cross-section: 35 mm²
  • Conductor diameter: 7.8 mm
  • Minimum insulation thickness: 0.9 mm
  • Ground conductor cross-section: 25 mm²
  • Minimum outer sheath thickness: 1.3 mm
  • Diameter over Sheath: 29.3 mm
  • Approximate weight: 1791 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x50+1x25 mm2 FB

Nexans ref. P00020451-9 - Country ref. 10040103

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 50 mm²
  • Conductor diameter: 9.4 mm
  • Minimum insulation thickness: 1.0 mm
  • Ground conductor cross-section: 25 mm²
  • Minimum outer sheath thickness: 1.3 mm
  • Diameter over Sheath: 29.5 mm
  • Approximate weight: 1912 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x50+1x50 mm2 FB

Nexans ref. P00010391-8 - Country ref. 10047235

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 50 mm²
  • Conductor diameter: 9.4 mm
  • Minimum insulation thickness: 1.0 mm
  • Ground conductor cross-section: 50 mm²
  • Minimum outer sheath thickness: 1.4 mm
  • Diameter over Sheath: 31.3 mm
  • Approximate weight: 2165 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x70+1x35 mm2 FB

Nexans ref. P00020447-13 - Country ref. 10040048

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 70 mm²
  • Conductor diameter: 11.2 mm
  • Minimum insulation thickness: 1.1 mm
  • Ground conductor cross-section: 35 mm²
  • Minimum outer sheath thickness: 1.5 mm
  • Diameter over Sheath: 34.3 mm
  • Approximate weight: 2668 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x70+1x70 mm2 FB

Nexans ref. P00020691-7 - Country ref. 10046826

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 70 mm²
  • Conductor diameter: 11.2 mm
  • Minimum insulation thickness: 1.1 mm
  • Ground conductor cross-section: 70 mm²
  • Minimum outer sheath thickness: 1.6 mm
  • Diameter over Sheath: 36.6 mm
  • Approximate weight: 3035 kg/km

 

RETFLEX N2XY 0,6/1 kV 4x70+1x35 mm2 FB

Nexans ref. P00006755-2 - Country ref. 10032871

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 4
  • Conductor cross-section: 70 mm²
  • Conductor diameter: 11.3 mm
  • Minimum insulation thickness: 1.1 mm
  • Ground conductor cross-section: 35 mm²
  • Minimum outer sheath thickness: 1.6 mm
  • Diameter over Sheath: 41.2 mm
  • Approximate weight: 3500 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x95+1x50 mm2 FB

Nexans ref. P00020450-7 - Country ref. 10040052

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 95 mm²
  • Conductor diameter: 13.1 mm
  • Minimum insulation thickness: 1.1 mm
  • Ground conductor cross-section: 50 mm²
  • Minimum outer sheath thickness: 1.6 mm
  • Diameter over Sheath: 39.1 mm
  • Approximate weight: 3529 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x95+1x70 mm2 FB

Nexans ref. P00023712-2 - Country ref. 10053858

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 95 mm²
  • Conductor diameter: 13.1 mm
  • Minimum insulation thickness: 1.1 mm
  • Ground conductor cross-section: 70 mm²
  • Minimum outer sheath thickness: 1.6 mm
  • Diameter over Sheath: 40.1 mm
  • Approximate weight: 3740 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x120+1x70 mm2 FB

Nexans ref. P00020448-11 - Country ref. 10040049

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 120 mm²
  • Conductor diameter: 14.7 mm
  • Minimum insulation thickness: 1.2 mm
  • Ground conductor cross-section: 70 mm²
  • Minimum outer sheath thickness: 1.7 mm
  • Diameter over Sheath: 43.8 mm
  • Approximate weight: 4544 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x120+1x50mm2 FB

Nexans ref. P00035113-1 - Country ref. 10050344

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 120 mm²
  • Conductor diameter: 14.7 mm
  • Minimum insulation thickness: 1.2 mm
  • Ground conductor cross-section: 50 mm²
  • Minimum outer sheath thickness: 1.7 mm
  • Diameter over Sheath: 42.8 mm
  • Approximate weight: 4637 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x120+1x120 mm2 FB

Nexans ref. P00012854-5 - Country ref. 10046713

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 120 mm²
  • Conductor diameter: 14.7 mm
  • Minimum insulation thickness: 1.2 mm
  • Ground conductor cross-section: 120 mm²
  • Minimum outer sheath thickness: 1.8 mm
  • Diameter over Sheath: 46.2 mm
  • Approximate weight: 5046 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x150+1x70mm2 FB

Nexans ref. P00012395-7 - Country ref. 10045083

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 150 mm²
  • Conductor diameter: 16.5 mm
  • Minimum insulation thickness: 1.4 mm
  • Ground conductor cross-section: 70 mm²
  • Minimum outer sheath thickness: 1.9 mm
  • Diameter over Sheath: 48.5 mm
  • Approximate weight: 5552 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x150+1x150 mm2 FB

Nexans ref. P00012856-4 - Country ref. 10049077

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 150 mm²
  • Conductor diameter: 16.5 mm
  • Minimum insulation thickness: 1.4 mm
  • Ground conductor cross-section: 150 mm²
  • Minimum outer sheath thickness: 2.0 mm
  • Diameter over Sheath: 51.8 mm
  • Approximate weight: 6355 kg/km

 

RETFLEX N2XY 0,6/1 kV 4x150+1x70mm2 FB

Nexans ref. P00038680-0 - Country ref. 10053184

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 4
  • Conductor cross-section: 150 mm²
  • Conductor diameter: 16.5 mm
  • Minimum insulation thickness: 1.4 mm
  • Ground conductor cross-section: 70 mm²
  • Minimum outer sheath thickness: 2.1 mm
  • Diameter over Sheath: 57.4 mm
  • Approximate weight: 7033 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x185+1x50 mm2 FB

Nexans ref. P00040019-0 - Country ref. 10054463

  • Packaging: Cut to length (m)
  • Outer sheath: PVC
  • Number of cores: 3
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 18.1 mm
  • Minimum insulation thickness: 1.6 mm
  • Ground conductor cross-section: 50 mm²
  • Minimum outer sheath thickness: 2.0 mm
  • Diameter over Sheath: 51.9 mm
  • Approximate weight: 6328 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x185+1x70 mm2 FB

Nexans ref. P00028400-4 - Country ref. 10050345

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 18.1 mm
  • Minimum insulation thickness: 1.6 mm
  • Ground conductor cross-section: 70 mm²
  • Minimum outer sheath thickness: 2.0 mm
  • Diameter over Sheath: 52.9 mm
  • Approximate weight: 6558 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x185+1x95 mm2 FB

Nexans ref. P00020449-8 - Country ref. 10040051

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 18.1 mm
  • Minimum insulation thickness: 1.6 mm
  • Ground conductor cross-section: 95 mm²
  • Minimum outer sheath thickness: 2.0 mm
  • Diameter over Sheath: 53.8 mm
  • Approximate weight: 6794 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x185+1x120 mm2 FB

Nexans ref. P00028333-5 - Country ref. 10050849

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 18.1 mm
  • Minimum insulation thickness: 1.6 mm
  • Ground conductor cross-section: 120 mm²
  • Minimum outer sheath thickness: 2.0 mm
  • Diameter over Sheath: 54.7 mm
  • Approximate weight: 7056 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x240+1x120mm2 FB

Nexans ref. P00012410-6 - Country ref. 10045071

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 20.9 mm
  • Minimum insulation thickness: 1.7 mm
  • Ground conductor cross-section: 120 mm²
  • Minimum outer sheath thickness: 2.2 mm
  • Diameter over Sheath: 60.9 mm
  • Approximate weight: 8872 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x240+1x240mm2 FB

Nexans ref. P00017159-1 - Country ref. 10055585

  • Packaging: Cut to length (m)
  • Outer sheath: PVC
  • Number of cores: 3
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 20.9 mm
  • Minimum insulation thickness: 1.7 mm
  • Ground conductor cross-section: 240 mm²
  • Minimum outer sheath thickness: 2.3 mm
  • Diameter over Sheath: 64.9 mm
  • Approximate weight: 10189 kg/km

 

RETFLEX N2XY 0,6/1 kV 3x300+1x150mm2 FB

Nexans ref. P00012869-4 - Country ref. 10051417

  • Packaging: Cut to length (m)
  • Outer sheath: PVC Flexible
  • Number of cores: 3
  • Conductor cross-section: 300 mm²
  • Conductor diameter: 23.3 mm
  • Minimum insulation thickness: 1.8 mm
  • Ground conductor cross-section: 150 mm²
  • Minimum outer sheath thickness: 2.4 mm
  • Diameter over Sheath: 67.3 mm
  • Approximate weight: 11035 kg/km

 

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-1-2; IEC 60502-1; IEC 60811-401; IEC 60811-402; IEC 60811-409; IEC 60811-501; IEC 60811-502; IEC 60811-504; IEC 60811-505; IEC 60811-506; IEC 60811-507; IEC 60811-508; IEC 60811-509
  • National
    NTP-IEC 60228; NTP-IEC 60502-1; UL 2556

Application:

General application as power cable. In low voltage distribution power networks, industrial installations, in buildings and operation stations. In fixed installations, indoor and outdoor areas (trays, gutters, staples). It can be installed in ducts, in dry or wet locations.

Construction:

1. Conductor: Flexible soft copper, class 5.

2. Insulation: Cross linked polyethylene XLPE.

3. Insulated grounding conductor: Flexible soft copper, class 5 - XLPE

4. Filler: Flexible compound polyvinyl chloride PVC (when applicable).

5. Outer sheath: Flexible compound polyvinyl chloride PVC.

Main characteristics:

Good electrical and mechanical properties. Cross-linked polyethylene insulation allows greater power capacity under any operating condition, minimum dielectric losses, high insulation resistance. The PVC outer sheath allows an adequate resistance to greases, oils, abrasion and sunlight. Flame retardant.

Cross section:

From 4 mm2 up to 300 mm2.

Marking:

INDECO S.A. RETFLEX N2XY 0,6/1 kV - Nb. Cores x section + Grounding Cond. Section - 90C - Year (- sequential length m. || sequential length m. + ) .

Packing:

Non returnable wooden reels.

Colour:

Insulation: See core identification.

Outer sheath: Black.

National standards

NTP-IEC 60228: Conductors of insulated cables.

NTP-IEC 60502-1: Power cables with extruded insulation and their accessories for rated voltages from 1 kV and 3 kV.

International standards

IEC 60228: Conductors of insulated cables.

IEC 60502-1: Power cables with extruded insulation and their accessories for rated voltages from 1 kV and 3 kV.

IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame.

UL 2556: Wire and Cable Test Methods. Section 9.3:FT1 (Vertical-Specimen) Flame Test.

IEC 60811-401: Thermal ageing methods -Ageing in an air oven.

IEC 60811-402: Water absorption test.

IEC 60811-409: Mass loss test for thermoplastic insulations and covers.

IEC 60811-501: Test for determining the mechanical properties of insulating and sheating.

IEC 60811-502: Shrinkage test for isolations.

IEC 60811-504: Bending test at low temperature for insulation and covers.

IEC 60811-505: Low temperature elongation test for insulations and covers.

IEC 60811-506: Impact test at low temperature for insulations and covers.

IEC 60811-507: Hot elongation test for crosslinked materials.

IEC 60811-508: High temperature pressure tests for insulations and covers.

IEC 60811-509: Tests of resistance to cracking of the insulations and covers (thermal shock).

UL 2556: Wire and Cable Test Methods. Section 4.2.8.5:Carbon-Arc and Xenon-Arc Tests- Sunlight resistance.

Core Identification I

Number of cores Core identification

2+T

White + Black + green

3+T

White + Black + Red + green
4+T

White + Black + Red + Blue + green

Calculation of Current Condition: Copper Conductor Multi-core L.V.; 90°C

CURRENT CAPACITY VALUES AND CURRENT CALCULATION CONDITIONS BASED ON IEC 60364-5-52:2009 :

TABLE B.52.5 (METHOD D1: Buried ducts in triangular formation).
TABLE B.52.5 (METHOD D2: Buried in triangular formation).
TABLE B.52.12 (METHOD E: Air in tringular formation).

Maximum conductor temperature : 90°C.
Ambient air temperature : 30°C.
Ground temperature : 20°C.
Depth of laying up to: 0,7 m.
Thermal resistivity of soil : 2,5 K.m/W.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Insulating material
XLPE
Sheath colour
Black
Lead free
Yes
Conductor flexibility
Class 5 IEC 60228

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Dielectric strength
3.5 kV
Time of application Dielectric strength core to screen AC
5 min.

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Excellent

Usage characteristics

Usage characteristics

Flame retardant
IEC 60332-1-2; FT1
Oil resistance
Good
Water proof
AD8 according to UNE-EN 50525-2-21
Metric marking
Double marking of sequential footage METRIUM
U.V resistance
UL 2556 - Sunlight Resistance
Maximum operating temperature
90 °C
Overload maximum core temperature
130 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Documentation

xlsx — 0 B

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close