FREETOX NA2XOH 1,8/3 kV; NMX-J-142/1-ANCE; Resist. UV

Description
Special application in places with poor ventilation and places public attendance high.

Description
Description
Application:
In low voltage power distribution networks. Special application in places with poor ventilation, direct application in places with public attendance high. It can be installed in ducts or directly underground in dry and wet places.
Construction:
1. Conductor: Aluminium 1350, class D.
2. Insulation: Halogen free, anti-flame cross linked polyethylene XLPE.
3. Outer sheath: thermoplastic compound HFFR-UV.
Main characteristics:
The cable has excellent electric properties. The cross-linked polyethylene insulation allows a higher power capacity current under any operation conditions, lower dielectric losses, high insulation resistance. The outer sheath has the following characteristics: Fire retardant, low emission dense smoke and halogen free. Adequate resistance to oils. Resistance to sunlight.
Gauge:
500 kcmil.
Marking:
INDECO S.A. FREETOX NA2XOH 1,8/3 kV - Gauge -Year - Sequential length.
Packing:
Non returnable wooden reels.
Colour:
Insulation: Black.
Outer sheath: Black-UV.
Standards
IEC 60502-1: Power cables with extruded insulation and their accesories for rated voltages from 1 kV and 3kV.
NMX-J-032-ANCE: Wires and cables – Concentric Lay Stranded Aluminum 1350 cable for electrical purposes – Specifications.
NMX-J-040-ANCE: Determination of moisture absorption in isolates.
NMX-J-093-ANCE: Determination of resistance to fire propagation.
NMX-J-142/1-ANCE: Wires and cables-Shielded power cables, rated 5 kV through 35 kV, cross-linked polyethylene or ethylene-propylene rubber insulated-specifications and test methods.
NMX-J-177-ANCE: Determination of thicknesses of semiconductor screens, insulation and covers.
NMX-J-178-ANCE: Determination of stress and stress elongation at breakdown of insulation, semiconductor screens and covers of electrical conductors.
NMX-J-186-ANCE: Accelerated Aging in Furnace to semiconductor screens, insulation and protective covers of electrical conductors.
NMX-J-192-ANCE: Resistance to flame propagation.
NMX-J-193-ANCE: Cold bending of insulation and non-metallic protective covers for electrical conductors.
NMX-J-194-ANCE: Accelerated aging in oil for insulation and protective covers of electrical conductors.
NMX-J-212-ANCE: Electric resistance, resistivity and conductivity.
NMX-J-293-ANCE: Stamina from dielectric to electric tension.
NMX-J-294-ANCE: Insulation resistance.
NMX-J-432-ANCE: Determination of the hot elongation and permanent deformation of crosslinked materials.
NMX-J-472-ANCE: Determination of the amount of halogenated acid gas and the degree of acidity of the gases released during the combustion of polymeric materials.
NMX-J-474-ANCE: Determination of the specific optical density and of the smoke darkening value generated in electrical conductors.
NMX-J-498-ANCE: Determination of the resistance to flame propagation in electrical conductors that are placed in a vertical tray.
NMX-J-553-ANCE: Weather resistance of insulation or cover.
NMX-J-555-ANCE: Wires and cables – Power cables for rated voltage: 1 kV, 240 mm2 with halogen free cross linked extruded, for electric traction in mass transit systems installations – Specifications.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Aluminum Alloy 1350 |
Insulating material | Halogen free flame retardant XLPE |
Insulation colour | Black |
Outer sheath | Halogen free thermoplastic compound - UV Resist. |
Sheath colour | Black - UV |
Halogen free | NMX-J-472-ANCE |
Electrical characteristics | |
Dielectric strength | 6.5kV |
Time of application Dielectric strength core to screen DC | 5min. |
Usage characteristics | |
U.V resistance | NMX-J-553-ANCE |
Oil resistance | NMX-J-194-ANCE |
Gases toxicity | Low |
Gases corrosivity | Low acidity NMX-J-472-ANCE |
Smoke density | Low NMX-J-474-ANCE |
Flame retardant | NMX-J-192-ANCE |
Fire retardant | NMX-J-498-ANCE |
Maximum operating temperature | 90°C |
Overload maximum core temperature | 130°C |
Short-circuit max. conductor temperature | 250°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
-
BENDING RADIUS INSTALLED IN M.V
R=Dxf
R: Bending radius when installed (mm)
D: Diameter over sheath (mm)
f: Multiplicative factor; given the following table:
-
Calculation of Current Condition 1,8/3 kV Aluminium conductor
CALCULATION OF CURRENT CONDITION
BASED ON NEC TABLES 310.68 (IN AIR TREFOIL FORMATION), 310.82 (DIRECTLY BURIED FLAT FORMATION) AND 310.86 (DIRECTLY BURIED TREFOIL FORMATION)
Horizontal flat formation clearance: 0.2 m.
Maximum conductor temperature: 90°C.
Ambient air temperature: 40°C.
Ground temperature: 20°C.
Depth of laying: 0.9 m.
Thermal resistance: 0.9 K.m/W.