FREETOX N2XOH-C 600 V; UV. Resist.

Description
Special application in places with poor ventilation and high public attendance.

Description
Standards
International : IEC 60332-1-2; IEC 60332-3-24 Cat.C; IEC 60684-2; IEC 60754-1; IEC 60754-2; IEC 61034-2National : ASTM B 8; ICEA S-95-658; UL 2556
Description
Application:
In industrial plants, for systems of motor control, lighting, signaling and overal equipment interconnection, control circuits of automatic machines. Direct application in places with high public attendance.
Construction:
1. Conductor: Compress soft copper, class B.
2. Insulation: Cross linked polyethylene XLPE.
3. Outer sheath: HFFR-UV halogen free thermoplastic compound..
Main characteristics:
Lower dielectric losses, high insulation resistance. The outer sheath has the following characteristics: Fire retardant, low emission dense smoke and halogen free. Easy installation. Adequate resistance to oils. Resistance to sunlight.
Gauge:
14 AWG and 12 AWG.
Marking:
INDECO S.A. FREETOX N2XOH-C 600 V - N° conductors x Gauge - Year - Sequential length.
Packing:
Non returnable wooden reels.
Colour:
Insulation: Black with white numbers.
Outer sheath: Black-UV.
International standards
ASTM B8: Concentric-lay-stranded copper conductors, hard, medium-hard, or soft.
ICEA S-95-658: Power cables rated 2000 volts or less for the distribution of electrical energy.
IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame.
UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame Test.
IEC 60332-3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category C.
IEC 60684-2: Flexible insulating sleeving - Part 2: Methods of test.
IEC 60754-1: Test on gases evolved during combustion of materials from cables - Part 1: Determination of the halogen acid gas content.
IEC 60754-2: Test on gases evolved during combustion of materials from cables - Part 2: Determination of acidity (by pH measurement) and conductivity.
IEC 61034-2: Measurement of smoke density of cables burning under defined conditions.
ICEA S-95-658: Power cables rated 2000 volts or less for the distribution of electrical energy. Section 6.4.2: Oil Immersion Test.
UL 2556: Wire and Cable Test Methods. Section 4.2.8.5: Carbon-Arc and Xenon-Arc Tests- Sunlight resistance.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Soft copper |
Insulating material | XLPE |
Outer sheath | Halogen free thermoplastic compound - UV Resist. |
Sheath colour | Black - UV |
Halogen free | IEC 60754-1 |
Electrical characteristics | |
Dielectric strength | 3.5kV |
Time of application Dielectric strength core to screen DC | 5min. |
Usage characteristics | |
U.V resistance | UL 2556 - Sunlight Resistance |
Gases toxicity | Low toxicity to IEC 60684-2 |
Gases corrosivity | Low pH Corrosivity IEC 60754-2 |
Oil resistance | ICEA S-95-658 |
Smoke density | IEC 61034-2 |
Flame retardant | IEC 60332-1-2; FT1 |
Fire retardant | IEC 60332-3-24 Cat.C |
Maximum operating temperature | 90°C |
Overload maximum core temperature | 130°C |
Short-circuit max. conductor temperature | 250°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
-
BENDING RADIUS WHEN INSTALLED IN L.V.
R=Dxf
R: Bending radius when installed (mm)
D: Diameter over sheath or over insulation (when it has not sheath) (mm)
f: Multiplicative factor; given the following table:
-
Calculation of Current Condition L.V. AWG - Control cables
CALCULATION OF CURRENT CONDITION BASED ON NEC TABLE B.310.3
Maximum conductor temperature: 90°C
For other ambient temperatures see table B.310.3, correction factors.