FREETOX NH-80 450/750 V; Grounding conductor

Description
Special application in places with poor ventilation and places public attendance high.

Description
Standards
International : IEC 60228; IEC 60332-1-2; IEC 60332-3-24 Cat.C; IEC 60684-2; IEC 60754-1; IEC 60754-2; IEC 61034-2National : NTP 370.252; NTP-IEC 60228; UL 2556
Description
Application:
Special application in places with poor ventilation, where, in case of fire, the emission of corrosive, toxic gases and smoke threatens life and destroys electrical and electronic equipment, for example in residential buildings, offices, industrial plants, movie, theaters, discotheques, hospitals, airports, underground stations, etc. In case of fire, possible victims have higher chances of surviving because they don't breath in toxic gases and have good visibility to escape the area. They are usually installed in conduits and in indoor areas in tray. Not recommended for outdoor installations. Not recommended for outdoor installations.
Construction:
Conductor: Compact soft copper, class 2.
Insulation: Halogen free thermoplastic compound HFFR.
Main characteristics:
Fire retardant, low emission dense smoke and halogen free.
Cross section:
120 mm2.
Marking:
INDECO S.A. FREETOX NH-80 450/750 V - Section - Year - Sequential length..
Packing:
Non returnable wooden reels.
Colour:
Yellow/Green.
National standards
NTP-IEC 60228: Conductors of insulated cables.
NTP 370.252: Thermoplastic and thermoset insulated cables of rated voltages up to and including 450/750 V.
NTP 370.266-3-31: Low voltage electrical cables. Cable with nominal voltage less than or equal to 450/750 V . Part 3-31: Cables with special properties before the fire. Single core cables without cover with halogen-free thermoplastic insulation and low smoke emission.
NTP 370.264-7: Insulation, covering and coating materials for low voltage electrical power cables. Part 7: Halogen-free thermoplastic compounds for insulation.
International standards
IEC 60228: Conductors of insulated cables.
IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame.
UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame Test.
IEC 60332-3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category C.
IEC 60684-2: Flexible insulating sleeving - Part 2: Methods of test.
IEC 60754-1: Test on gases evolved during combustion of materials from cables - Part 1: Determination of the halogen acid gas content.
IEC 60754-2: Test on gases evolved during combustion of materials from cables - Part 2: Determination of acidity (by pH measurement) and conductivity.
IEC 61034-2: Measurement of smoke density of cables burning under defined conditions.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Soft copper |
Insulation | Halogen free thermoplastic material |
Halogen free | IEC 60754-1 |
Colour | Yellow / green |
Lead free | Yes |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 450 / 750 V |
Dielectric strength | 2.5kV |
Time of application Dielectric strength core to screen DC | 5min. |
Usage characteristics | |
Gases toxicity | Low toxicity to IEC 60684-2 |
Gases corrosivity | Low pH Corrosivity IEC 60754-2 |
Smoke density | IEC 61034-2 |
Flame retardant | IEC 60332-1-2; FT1 |
Fire retardant | IEC 60332-3-24 Cat.C |
Minimum operating temperature | -40°C |
Maximum operating temperature | 80°C |
Overload maximum core temperature | 100°C |
Short-circuit max. conductor temperature | 160°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
-
BENDING RADIUS WHEN INSTALLED IN L.V.
R=Dxf
R: Bending radius when installed (mm)
D: Diameter over sheath or over insulation (when it has not sheath) (mm)
f: Multiplicative factor; given the following table:
-
Calculation of Current Condition L.V.; 80°C
CALCULATION OF CURRENT CONDITION
Maximum conductor temperature : 80°C.
Ambient air temperature : 30°C.