Description
Standards
International : IEC 60228; IEC 60332-1-2; IEC 60502-1; IEC 60811-401; IEC 60811-402; IEC 60811-501; IEC 60811-504; IEC 60811-505; IEC 60811-506; IEC 60811-508; IEC 60811-509National : ICEA S-95-658; NTP-IEC 60228; NTP-IEC 60502-1; UL 2556
Description
Application:
In factories, for systems of motor control, lighting, signaling and overal equipment interconnection, control circuits of automatic machines.
Construction:
1. Conductor: Compressed soft copper, class 2.
2. Insulation: Compound polyvinyl chloride PVC.
3. Outer sheath: Compound polyvinyl chloride PVC.
Main characteristics:
Resistance to abrasion, moisture and sunlight. Adequate resistance to grease and oil. Easy installation. Resistance to sunlight. Flame retardant.
Cross section:
From 1,5 mm2 up to 6 mm2.
Marking:
INDECO S.A. NYY(80º)-C 0,6/1 kV - Nb. Conductors x Section - Year - Sequential length.
Packing:
Non returnable wooden reels.
Colour:
Insulation: Black with white numbers.
Outer sheath: Black.
National standards
NTP-IEC 60228: Conductors of insulated cables.
NTP-IEC 60502-1: Power cables with extruded insulation and their accessories for rated voltages from 1 kV and 3 kV.
International standards
IEC 60228: Conductors of insulated cables.
IEC 60502-1: Power cables with extruded insulation and their accessories for rated voltages from 1 kV and 3 kV.
IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame.
UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame Test.
IEC 60811-401: Thermal ageing methods. Ageing in an air oven.
IEC 60811-402: Water absorption tests.
IEC 60811-501: Test for determining the mechanical properties.
IEC 60811-504: Bending test at low temperature for insulation and sheaths.
IEC 60811-505: Elongation at low temperature for insulations and sheaths.
IEC 60811-506: Impact test at low temperature for insulations and sheaths.
IEC 60811-508: Pressure test at high temperature for insulation and sheaths.
IEC 60811-509: Test for resistance of insulations and sheaths to cracking.
ICEA S-95-658: Power cables rated 2000 volts or less for the distribution of electrical energy. Section 6.4.2: Oil Immersion Test.
UL 2556:Wire and Cable Test Methods. Section 4.2.8.5: Carbon-Arc and Xenon-Arc Tests- Sunlight resistance.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Soft copper |
Insulating material | PVC |
Core identification | Black cores with white numbers |
Outer sheath | PVC |
Sheath colour | Black |
Number of conductors | 4 |
Lead free | Yes |
Dimensional characteristics | |
Conductor cross-section | 2.5mm² |
Conductor diameter | 1.9mm |
Minimum insulation thickness | 0.8mm |
Minimum outer sheath thickness | 1.2mm |
Diameter over Sheath | 11.3mm |
Approximate weight | 203kg/km |
Total number of wires | 7 |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/ 1 (1.2) kV |
Dielectric strength | 3.5kV |
Time of application Dielectric strength core to screen DC | 5min. |
Max. DC resistance of the conductor at 20°C | 7.41Ohm/km |
Perm current rating in air 30°C | 19A |
Nominal capacitance | 695.0pF/m |
Usage characteristics | |
U.V resistance | UL 2556 - Sunlight Resistance |
Flame retardant | IEC 60332-1-2; FT1 |
Oil resistance | ICEA S-95-658 |
Maximum operating temperature | 80°C |
Overload maximum core temperature | 100°C |
Short-circuit max. conductor temperature | 160°C |
Docs and info
-
BENDING RADIUS WHEN INSTALLED IN L.V.
R=Dxf
R: Bending radius when installed (mm)
D: Diameter over sheath or over insulation (when it has not sheath) (mm)
f: Multiplicative factor; given the following table:
-
Calculation of Current Condition L.V.; 80°C
CALCULATION OF CURRENT CONDITION
Maximum conductor temperature : 80°C.
Ambient air temperature : 30°C.