CAI 0,6/1 kV Covered Neutral without Public Lighting

Products

CAI 0,6/1 kV 1x10+NA10 mm2

Nexans ref. P00016807-1-M

  • Number of cores: 1
  • Phase Conductor Cross Section: 10 mm²
  • Phase Conductor Diameter: 3.9 mm
  • Minimum insulation thickness: 1.14 mm
  • Neutral conductor section (when smaller): 10 mm²
  • Nominal outer diameter: 12.7 mm
  • Approximate weight: 220 kg/km

 

CAI 0.6/1 kV 1x16+NA16 mm2

Nexans ref. P00016808-1-M

  • Number of cores: 1
  • Phase Conductor Cross Section: 16 mm²
  • Phase Conductor Diameter: 4.93 mm
  • Minimum insulation thickness: 1.14 mm
  • Neutral conductor section (when smaller): 16 mm²
  • Nominal outer diameter: 14.8 mm
  • Approximate weight: 337 kg/km

 

CAI 0,6/1 kV 3x16+NA25 mm2

Nexans ref. P00032496-0-M

  • Number of cores: 3
  • Phase Conductor Cross Section: 16 mm²
  • Phase Conductor Diameter: 4.9 mm
  • Minimum insulation thickness: 1.14 mm
  • Neutral conductor section (when smaller): 25 mm²
  • Nominal outer diameter: 18.5 mm
  • Approximate weight: 762 kg/km

 

CAI 0,6/1 kV 3x35+NA35 mm2

Nexans ref. P00016456-1-M

  • Number of cores: 3
  • Phase Conductor Cross Section: 35 mm²
  • Phase Conductor Diameter: 7.3 mm
  • Minimum insulation thickness: 1.14 mm
  • Neutral conductor section (when smaller): 35 mm²
  • Nominal outer diameter: 23.5 mm
  • Approximate weight: 1408 kg/km

 

CAI 0,6/1 kV 3x50+NA50 mm2

Nexans ref. P00016457-1-M

  • Number of cores: 3
  • Phase Conductor Cross Section: 50 mm²
  • Phase Conductor Diameter: 8.6 mm
  • Minimum insulation thickness: 1.52 mm
  • Neutral conductor section (when smaller): 50 mm²
  • Nominal outer diameter: 28.8 mm
  • Approximate weight: 1925 kg/km

 

CAI 0,6/1 kV 3x70+NA70 mm2

Nexans ref. P00016458-1-M

  • Number of cores: 3
  • Phase Conductor Cross Section: 70 mm²
  • Phase Conductor Diameter: 10.3 mm
  • Minimum insulation thickness: 1.52 mm
  • Neutral conductor section (when smaller): 70 mm²
  • Nominal outer diameter: 33.0 mm
  • Approximate weight: 2729 kg/km

 

Description

Description

Standards

  • International
    IEC 60228; IEC 60811-401; IEC 60811-402; IEC 60811-501; IEC 60811-502; IEC 60811-507; IEC 60811-511
  • National
    NTP 370.251; NTP 370.254; NTP-IEC 60228

 

Application:

For urban and rural overhead secundary distribution networks, with voltages up to 1000 V.

 

Construction:

1. Conductor: Soft copper, class 2.

2. Neutral messenger: Hard copper - XLPE.

3. Insulation: Cross linked polyethylene XLPE.

 

Main characteristics:

Increased current capacity, high insulation resistance and lower inductive reactance than with CPI conductors, higher conductivity and lower energy loss, used in overhead distribution lines. Increased safety due to its mechanical strength and toughness of the insulation. Insulators are not necessary for installation. Resistance to abrasion, weather and sunlight.

Cross section:

From 10 mm2 up to 70 mm2.

Marking:

INDECO S.A. CAI 0.6/1 kV (Nb. Cores x Section)+ NA(Neutral messenger section)- Year - Sequential length.

Packing:

Non returnable wooden reels.

Colour:

Black, see core identification.

 

National standards

NTP-IEC 60228: Conductors of insulated cables.

NTP 370.254: Cables for overhead distribution networks self-supporting XLPE insulated of rated voltages up to and including 0.6/1 kV.

NTP 370.251: Copper cables for overhead (bare or protected) and grounded. 

 

International standards

IEC 60228: Conductors of insulated cables.

IEC 60811-201: Measurement of insulation thickness.

IEC 60811-401: Thermal ageing methods -Ageing in an air oven.

IEC 60811-402: Water absorption test.

IEC 60811-501: Test for determining the mechanical properties of insulating and sheating.

IEC 60811-502: Shrinkage test for isolations.

IEC 60811-507: Hot elongation test for crosslinked materials.

IEC 60811-511: Measurement of hot melt index of polyethylene compounds.

BENDING RADIUS WHEN INSTALLED

R = f x D
R: Bending radius when installed (mm).
f: Multiplicative factor.
D: Cable nominal outer diameter (mm).

Calculation of Current Condition overhead secondary distribution

CALCULATION OF CURRENT CONDITION

Maximum conductor temperature : 90°C.
Ambient air temperature : 30°C.
Speed of cross wind: 2 km/h.
Bundled conductors.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Insulating material
XLPE
Core identification
Rib markings
Neutral messenger
Hard Copper conductor

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Dielectric strength
4.0 kV
Time of application Dielectric strength core to screen DC
5 min.

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Class 2 IEC 60228

Usage characteristics

Usage characteristics

Bending factor when installed
4 (xD)
U.V resistance
Yes
Maximum operating temperature
90 °C
Overload maximum core temperature
130 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close