NA2XS2Y 19/33 kV WS+TS; IRAM 2178-2

Products

NA2XS2Y 19/33 kV 185 mm2 PHC50

Nexans ref. P00055181-0 - Country ref. 10057486

  • Packaging: Cut to length (m)

 

Description

Description

Application

Power distribution in medium voltage. As transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations.

CONSTRUCTION

1. Conductor: Compact stranded aluminium 1350, class 2.

2. Inner semi-conductor: Extruded.

3. Insulation: Cross linked polyethylene XLPE-TR (Tree retardant).

4. External semi-conductor: Extruded strippable.

These last three components extruded CV (continuous vulcanization) triple extrusion in dry cure process.

5. Screen: Copper wires + copper tape in open spiral.

6. Tape: Polyester.

7. Outer sheath: Linear low-density polyethylene LLDPE-UV.

MAIN CHARACTERISTICS

Excellent properties against heat aging. The outer sheath has the following characteristics: resistance to abrasion, moisture and sunlight. Adequate resistance to greases and oils. Low emission dense smoke and halogen free.

CROSS SECTION

185 mm2.

MARKING

INDECO BY NEXANS PERU NA2XSY 19/33 kV AL - N° Cores x Section + PH(Screen section) -  19/33 kV - CAT I - IRAM 2178 - EPESF - (LP N°## or CP N°##) - Year - Sequential length.

PACKING

Non returnable wooden reels.

COLOUR

Insulation: Natural.

Outer sheath: Black.

PRODUCT STANDARDS

NTP-IEC 60228: Conductors of insulated cables.

IEC 60228: Conductors of insulated cables.

IRAM 2178-2:Isolated Power Cables with Dielectric Solid Extruded for nominal voltages from 1,1 kV to 33 kV. Part 2: Power cables for nominal voltages from 3,3 kV (3,6 kV) to 33 kV (36 kV).

TESTING STANDARDS

IEC 60754-1: Test on gases evolved during combustion of materials from cables - Part 1: Determination of the halogen acid gas content.

IEC 60754-2: Test on gases evolved during combustion of materials from cables - Part 2: Determination of acidity (by pH measurement) and conductivity.

ICEA S-93-639: 5-46 kV Shielded Power Cable for Use in the Transmission and Distribution of Electric Energy - Section 9.4.2: Oil Immersion Test.

UL 2556: Wire and Cable Test Methods. Section 4.2.8.5: Carbon-Arc and Xenon-Arc Tests- Sunlight resistance. Section 9.3: FT1 (Vertical-Specimen) Flame Test.

Calculation of Current Condition Single core Medium Voltage - ABNT NBR 14039

CALCULATION OF CURRENT CONDITION BASED ON ABNT NBR 14039

Maximum conductor temperature: 90°C.
Ambient air temperature: 30°C.
Ground temperature: 20°C.
Depth of laying: 0,9 m.
Thermal resistivity of soil: 1,5 K.m/W.

RECOMMENDATION - M.V. CABLE ACCESSORIES

Technical information presented herein is for referential purposes. Actual dimensions and construction details will be available only with the test reports for each manufacturing order. For "Make To Stock" products it is recommended to measure relevant dimensions directly on the cable. Nexans will not assume responsibility for connector selection.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum Alloy 1350
Material of the inner semi-conductor
Extruded
Insulating material
XLPE-TR
Material of the external semi-conductor
Extruded strippable
Screen
Copper wires + copper tape
Outer sheath
LLDPE
Sheath colour
Black
Halogen free
Low content Halogen IEC 60754-1
Conductor flexibility
Class 2 IEC 60228
Conductor shape
Compact stranded

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
19 / 33 (36) kV
Dielectric strength core to screen AC
66.5 kV
Time of application Dielectric strength core to screen AC
5 min.
Voltage for partial discharge test
32.8 kV
Maximal partial discharge test
5 pC

Usage characteristics

Usage characteristics

Oil resistance
ICEA S-93-639
Gases corrosivity
Low Corrosivity IEC 60754-2
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close